Refrigerator Compressor Amp Calculator
What circuit does your fridge actually need?
Convert refrigerator wattage to running and starting amps, then size the dedicated circuit. Uses Ohm's law (Amps = Watts ÷ Volts), compressor surge multipliers, and NEC 210.19 continuous-load sizing (125%).
Three inputs.
Real circuit spec.
Wattage from the nameplate, voltage from the outlet, compressor type from the spec sheet.
Ohm's law. NEC sizing.
Running amps = watts ÷ volts. Surge multipliers come from compressor manufacturer ratings; circuit sizing follows NEC 210.19(A) and conductor ampacity from NEC 310.16.
- 01
Running amps (Ohm's law)
Amps = watts ÷ voltage. A 150W fridge on 120V draws 1.25 amps continuous.
- 02
Starting surge
Standard compressor: 4× running amps. Inverter: 1.75×. Variable speed: 2×. Brief but high — must not nuisance-trip the breaker.
- 03
Circuit per NEC 210.19
Required circuit = running amps × 125% safety margin. Round up to the next standard breaker size: 15, 20, 30, or 40A.
- 04
Wire gauge per NEC 310.16
14 AWG for 15A, 12 AWG for 20A, 10 AWG for 30A, 8 AWG for 40A. Derate for ambient temp and conductor count.
Frequently asked
Tools that pair with this one
Upgrading the kitchen? Shop side-by-side fridges.
Browse side-by-side refrigerators at Fridge.com — most ship with low-amperage inverter compressors that work on standard 15A circuits.
Browse side-by-side fridges